ABB PowerValue 11 RT Quick Manual

Kategorie
Zdroje nepřerušitelného napájení (UPS)
Typ
Quick Manual

l
un I Jet
, 
ИБ
П ABB Powervalue 11 RT (6-10 кВА) - руководство по эксплуатации. Юниджет
Постоянная ссылка на страницу: https://www.uni-jet.com/catalog/istochniki-
besperebojnogo-pitaniya/on-line-ibp-1-kva-10kva/abb-powervalue-11-rt.html
PowerValue 11 RT
6-10 kVA
Quick guide
Quick guide | PowerValue 11 RT 6-10 kVA 1
1
2
3
2 PowerValue 11 RT 6-10 kVA | Quick guide
4
5
Quick guide | PowerValue 11 RT 6-10 kVA 3
6
7
4 PowerValue 11 RT 6-10 kVA | Quick guide
Quick guide | PowerValue 11 RT 6-10 kVA 5
1en
es
da
zh
fr
ru
nl
de
pt
cz
el
it
sv
pl
PowerValue 11 RT 6-10 kVA
Quick guide 7
Kurzanleitung 21
Guide de référence rapide 35
Guida rapida 49
Guía rápida 63
Guia de consulta rápida 77
Pikaopas 91
Snabbinstruktion 105
Kvikguide 119
Rychlý průvodce 133
Краткое руководство 147
Skrócony podręcznik 161
速成指南 175
Σύντομος οδηγός 189
Beknopte installatiehandleiding 203
6 PowerValue 11 RT 6-10 kVA | Quick guide
Quick guide | PowerValue 11 RT 6-10 kVA 7
1en
PowerValue 11 RT 6-10 kVA
Quick guide
Safety instructions 8
Installation 13
Operation 15
Troubleshooting 17
8 PowerValue 11 RT 6-10 kVA | Quick guide
en
Safety instructions
Read carefully
Always follow the precautions and instructions described in this manual. Any
deviations from the instructions may result in electrical shock or cause accidental
load loss.
ABB DOES NOT TAKE ANY RESPONSIBILITY FOR DAMAGES CAUSED THROUGH INCORRECT
MANIPULATIONS OF THE UPS SYSTEM.
Safety notices
WARNING
WARNING INDICATES THE PRESENCE OF A HAZARD WHICH COULD
RESULT IN SEVERE INJURY AND/OR SERIOUS DAMAGE TO THE SYSTEM.
CAUTION
CAUTION INDICATES THE PRESENCE OF A HAZARD WHICH COULD
RESULT IN MINOR INJURY AND/OR DAMAGE TO THE PRODUCT.
NOTE
NOTE INDICATES THE PRESENCE OF A HAZARD WHICH COULD LEAD TO
PROPERTY DAMAGE.
Safety symbols
SAFETY WARNING: THE SYMBOL IS USED TO ALERT THE USER TO WARNINGS,
CAUTIONS AND NOTES.
DANGER: THE SYMBOL IS USED TO ALERT THE USER TO THE OCCURRENCE
OF ELECTRICAL LIVE PARTS WITH HAZARDOUS VOLTAGES.
Quick guide | PowerValue 11 RT 6-10 kVA 9
1en
Batteries
DANGER
WARNING
COMPONENTS INSIDE THE UPS ARE CONNECTED TO THE
BATTERY EVEN WHEN THE UPS IS DISCONNECTED FROM
THE MAINS POWER SUPPLY.
DANGER
WARNING
DISCONNECT THE BATTERIES BEFORE CARRYING OUT ANY
KIND OF SERVICE AND/OR MAINTENANCE. VERIFY THAT NO
CURRENT IS PRESENT AND NO HAZARDOUS VOLTAGE
EXISTS IN THE CAPACITOR OR BUS CAPACITOR TERMINALS.
DANGER
WARNING
A BATTERY CAN PRESENT A RISK OF ELECTRICAL SHOCK
AND HIGH SHORT CIRCUIT CURRENT. THE FOLLOWING
PRECAUTIONS MUST BE OBSERVED WHEN WORKING ON
BATTERIES:
REMOVE WATCHES, RINGS OR OTHER METAL OBJECTS
MAKE USE OF PROPER PPE (PERSONAL PROTECTION
EQUIPMENT) AS PER LOCAL POLICIES AND RULES
WEAR FLAME/ARC RESISTANT WHOLE BODY
CLOTHING
WEAR SUITABLE VOLTAGE RATED GLOVES
USE SAFETY DIELECTRIC FOOTWEAR
WEAR ARC FLASH FACE SHIELD
USE VOLTAGE RATED TOOLS
DO NOT LAY TOOLS OR METAL PARTS ON TOP OF
BATTERIES
DISCONNECT THE CHARGING SOURCE PRIOR TO
CONNECTING OR DISCONNECTING BATTERY TERMINALS.
DANGER
WARNING
THE BATTERY CIRCUIT IS NOT ISOLATED FROM THE INPUT
VOLTAGE. HAZARDOUS VOLTAGES MAY OCCUR BETWEEN
THE BATTERY TERMINALS AND THE GROUND. VERIFY THAT
NO VOLTAGE IS PRESENT BEFORE SERVICING.
WARNING
NEVER DISPOSE BATTERIES ON FIRE AS THEY MAY EXPLODE.
10 PowerValue 11 RT 6-10 kVA | Quick guide
en
WARNING
DO NOT OPEN OR MUTILATE THE BATTERIES.
WARNING
RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES.
CAUTION
REPLACE BATTERIES WITH THE SAME NUMBER AND SAME TYPE OF
BATTERIES.
Installation
DANGER
WARNING
DISPLAY A WARNING LABEL ON ALL PRIMARY POWER
ISOLATORS INSTALLED REMOTE FROM THE UPS AREA TO
WARN ELECTRICAL MAINTENANCE PERSONNELS THAT THE
CIRCUIT FEEDS A UPS.
MAKE SURE THAT WARNING LABEL CONTAINS THE
FOLLOWING TEXT OR EQUIVALENT: “ISOLATE THE UPS
(UNINTERRUPTIBLE POWER SUPPLY) BEFORE WORKING ON
THIS CIRCUIT”.
DANGER
WARNING
HIGH FAULT CURRENTS (LEAKAGE CURRENTS). BEFORE
CONNECTING THE MAINS ENSURE THAT THE UPS IS
GROUNDED!
DANGER
WARNING
DO NOT REMOVE ANY SCREWS FROM THE UPS SYSTEM OR
FROM THE BATTERY CABINET: DANGER OF ELECTRICAL
SHOCK.
Quick guide | PowerValue 11 RT 6-10 kVA 11
1en
DANGER
WARNING
WHEN OPENING OR REMOVING THE UPS-COVERS YOU ARE
EXPOSED TO DANGEROUS VOLTAGES.
DANGER
WARNING
RISK OF BACKFEED VOLTAGE, ISOLATE THE UPS INSTALLING
AN EXTERNAL ISOLATING DEVICE BETWEEN MAINS INPUT
AND UPS; BEFORE OPERATING ON THIS CIRCUIT, CHECK
FOR HAZARDOUS VOLTAGE.
WARNING
WATER CONDENSING MAY OCCUR IF THE UPS IS UNPACKED IN A VERY
LOW TEMPERATURE. IN THIS CASE IT IS NECESSARY TO WAIT UNTIL THE
UPS IS FULLY DRIED INSIDE OUT BEFORE PROCEEDING INSTALLATION
AND USE TO AVOID HAZARDS AND ELECTRIC SHOCK, WAIT UNTIL THE
UPS IS FULLY DRY BOTH INSIDE AND OUTSIDE BEFORE INSTALLING.
CAUTION
INDUCTIVE LOADS (FOR EXAMPLE MONITORS AND LASER PRINTERS)
HAVE A VERY HIGH POWER CONSUMPTION AT START-UP. IF CONNECTED
TO THE UPS, THE START-UP POWER OF SUCH LOADS MUST BE TAKEN
INTO CONSIDERATION WHEN CALCULATING THE CAPACITY OF THE UPS
TO PREVENT THE UPS FROM BEING OVERLOADED AND TURNED OFF.
NOTE
TO REDUCE THE RISK OF FIRE, CONNECT THE UPS TO A CIRCUIT
PROVIDED WITH BRANCH CIRCUIT OVERCURRENT PROTECTION WITH AN
AMPERE RATING IN ACCORDANCE WITH THE IEC/EN 60934 STANDARD OR
YOUR LOCAL ELECTRICAL CODE.
SEE TECHNICAL SPECIFICATIONS FOR RECOMMENDATIONS.
12 PowerValue 11 RT 6-10 kVA | Quick guide
en
Operation
CAUTION
DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE.
CAUTION
DO NOT DISCONNECT THE MAINS CABLE FROM THE UPS OR THE
BUILDING WIRING SOCKET DURING OPERATION AS THIS REMOVES THE
GROUND FROM THE UPS AND ALL CONNECTED LOADS.
CAUTION
SWITCH OFF THE CONNECTED LOADS BEFORE TURNING ON THE UPS.
THEN SWITCH ON THE LOADS ONE BY ONE AFTER THE UPS IS TURNED
ON. SWITCH OFF ALL OF THE CONNECTED LOADS BEFORE TURNING OFF
THE UPS.
CAUTION
REPLACE FUSES ONLY BY DEVICES OF THE SAME TYPE AND OF THE
SAME AMPERAGE TO AVOID FIRE HAZARDS.
NOTE
PRESS THE OFF BUTTON TO FULLY DISCONNECT THE UPS. WAIT UNTIL
THE UPS IS ON BYPASS OR ON STAND-BY MODE BEFORE
DISCONNECTING IT FROM THE MAINS.
NOTE
INDISCRIMINATE OPERATION OF SWITCHES MAY CAUSE OUTPUT LOSS OR
DAMAGE TO EQUIPMENT.
Quick guide | PowerValue 11 RT 6-10 kVA 13
1en
Installation
Planning before installation
Install the unit to a position where any danger to the UPS is minimized to ensure a
long service life:
Install the UPS indoors.
Leave 50cm of space on each side of the cabinet to enable cooling airflow and
ensure that the circulation of air to the ventilation slits is not obstructed.
Avoid excessively high temperature and excessive moisture
Make sure that the surface is solid and flat
Rack mount installation – requires rack mounting kit, to be purchased
separately
Identify the rail holes in the rack for positioning the cabinet. Position the rails in
the bottom of the 3U space for 6kVA units and 5U space for 10kVA units.
Slide the cabinet into the rack. (Fig.1)
If installing additional UPS units, repeat the steps above for each cabinet
Tower installation
PowerValue 11 RT 6 kVA
Carefully rotate the LCD control panel 90º to the right. (Fig.2)
Place the units to a vertical position.
Screw the supports to the sides of the unit. (Fig.3)
PowerValue 11 RT 10 kVA
Carefully rotate the LCD control panel 90º to the right in the top and bottom front
panels. (Fig.4)
Place the units to a vertical position.
Screw the supports to the sides of the unit. (Fig.5)
14 PowerValue 11 RT 6-10 kVA | Quick guide
en
Electrical connections
PowerValue 11 RT 6 kVA (see Fig.6)
Legend
1 GND contact
2 EPO
3 Parallel port
4 Output circuit breaker
5 Output sockets
6 SNMP/ AS400 slot
7 USB
8 RS232
9 Bypass
10 AC input
11 AC output
PowerValue 11 RT 10 kVA (see Fig.7)
Legend
1 SNMP/ AS400 slot
2 EPO
3 USB
4 Parallel port
5 Battery connector
6 GND contact
7 Output sockets
8 Output circuit breaker
9 AC output
10 Bypass
11 AC input
Quick guide | PowerValue 11 RT 6-10 kVA 15
1en
Operation
You can operate the UPS through the user-friendly display (see chapter 4 of the user
manual for a full list of possible operations).
Power on/off
Scroll up
Scroll down
Select / Edit
UPS start-up
To start up the UPS with mains supply:
1. Check that all cables are connected correctly and well-fixed mechanically.
2. Keep the power-on button pressed for longer than 1 second. The fans are
activated and the UPS will load for a few seconds.
3. The UPS performs a self-test and the LCD shows the default UPS status screen.
16 PowerValue 11 RT 6-10 kVA | Quick guide
en
To start up the UPS without mains supply (cold start):
1. Check that all cables are connected correctly and well-fixed mechanically.
2. Keep the power-on button pressed for longer than 1 second. The UPS is powered
on, the fans are activated and the LCD is turned on. The UPS performs a self-test
and shows the default UPS status screen.
3. Keep the power-on button pressed for longer than 1 second. The alarm buzzer
sounds for 1 second and the UPS starts up.
4. After a few seconds, the UPS transfers to battery-mode. When the UPS is
supplied with power from the mains, the UPS transfers to online-mode without
interruption in the output of the UPS.
UPS Shutdown
To shut down the UPS with mains supply:
1. If the UPS is working on bypass-mode, go to step 3.
2. If the UPS is on online-mode, keep the power-on button pressed for more than 3
seconds. The alarm buzzer will sound and the UPS will transfer to bypass-mode.
Note that the bypass is still energized.
3. Disconnect the mains power supply. The display will shut down and the output
voltage will be removed from the UPS output terminal.
4. In case bypass has been disabled through the Settings menu, keep the power-
on button pressed for longer than 3 seconds to shut down the UPS. The unit will
transfer from online to stand-by mode. Disconnect the input power cable and the
display will shut down.
To shut down the UPS without mains supply:
1. To power off the UPS, keep the power on/off button pressed for more than 3
seconds. The alarm buzzer will sound for 3 seconds and the output power will be
immediately cut-off.
2. The display will shut down and the output voltage will be removed from the UPS
output terminal.
Quick guide | PowerValue 11 RT 6-10 kVA 17
1en
Troubleshooting
Alarm and events indicate warnings and notify of errors or potential failures in the
system. The output of the UPS is not necessarily affected in case of an alarm but
taking the correct actions may prevent loss of power to the load. If the UPS system
does not operate correctly, attempt to solve the problem using the table below.
Alarm or Event Possible cause Remedy
Utility Abnormal
Alarm Code: 02
The input mains is out of the UPS
tolerance range
Check input mains condition
Site Wiring Fault
Alarm Code: 04
Site Fault detection is supported on
all-models when a Grounding Neutral
connection is present. Alarm will
trigger when the difference between
ground and neutral voltage is >15V.
Site Fault detection should be
enabled by default. It can be enabled
/ disabled from the LCD settings
menu.
Reconnect all input wires
Battery Disconnect
Alarm Code:11
Battery voltage is lower than the
batteries disconnected level defined
for this UPS. There could be a blown
fuse, intermittent battery connection
or disconnected battery cable.
Verify that all batteries are properly
connected.
If the condition persists, contact your
service representative.
Battery low
Alarm Code:12
The UPS is in battery-mode and the
battery autonomy is running low.
This warning is approximate and the
actual time to shut down may vary.
Depending on the UPS load and the
number of external battery modules
(EXBAT), the “Battery Low” warning
may occur before the batteries reach
25% capacity
Service Battery
Alarm Code:13
A battery string failure has been
detected and the battery charger has
been disabled until its replacement
Contact your service representative
Charger Fail
Alarm Code:15
Indicates a charger failure The UPS charger is turned off until
the next startup. Contact your
service representative
Battery Over Voltage
Alarm Code:16
Indicates that the battery voltage is
too high
The UPS will turn off the charger until
the battery voltage is normal
BUS Over Voltage
Alarm Code:21
Indicates an over voltage in the BUS
of the UPS.
The UPS transfers to Bypass-mode
if supporting the load
BUS Under Voltage
Alarm Code:22
Indicates an under voltage in the
BUS of the UPS.
The UPS transfers to Bypass-mode
if supporting the load
BUS Unbalance
Alarm Code:23
Indicates that the positive BUS
voltage and negative BUS voltage
are not symmetric
The UPS transfers to Bypass-mode
if supporting the load
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221

ABB PowerValue 11 RT Quick Manual

Kategorie
Zdroje nepřerušitelného napájení (UPS)
Typ
Quick Manual